Allen-Bradley LOGIX 5000 Reference Manual page 441

Controllers advanced process control and drives and equipment phase and sequence instructions
Hide thumbs Also See for LOGIX 5000:
Table of Contents

Advertisement

Equipment Phase Instructions
PXRQ Error Codes
ERR (hex)
EXERR (hex)
00
0000
01
0000
02
0000
03
0110
0210
0410
1010
1020
04
0002
0003
0004
0005
0006
05
0000
06
0000
07
0000
Affects Math Status Flags
No
Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
Description
The PXRQ instruction was aborted
before it sent the request to
FactoryTalk Batch software.
The PXRQ instruction was aborted
after it sent the request to FactoryTalk
Batch software
Two or more PXRQ instructions
executed at the same time using the
same request type
Communication error. The request
was not delivered because there is no
subscriber to the phase
Communication error. The request
was not delivered because there is no
connection to the Notify object.
Communication error. Delivery failed.
Communication error. The request
was not delivered because FactoryTalk
Batch software does not subscribe to
receive the external request.
FactoryTalk Batch software is not
attached to the phase.
The FactoryTalk Batch software
encountered an error while processing
the request.
The PXRQ instruction contains an
invalid value.
FactoryTalk Batch software is not in
the proper state to process the
request.
Two or more PXRQ instructions
executed at the same time using
different request types
Error storing to parameter tags at end
of request processing.
FactoryTalk Batch software received
the request but passed back an invalid
cookie.
PXRQ instruction sent an invalid
parameter to FactoryTalk Batch
software.
Communication lost while PXRQ is
waiting for response from the external
sequencer.
Recommended Action
None
None
Limit execution to one PXRQ instruction at a time.
Check that FactoryTalk Batch software is connected and
running.
Check the connection and communication path to
FactoryTalk Batch software.
Check the connection and communication path to
FactoryTalk Batch software.
Check the connection and communication path to
FactoryTalk Batch software.
Check the connection and communication path to
FactoryTalk Batch software.
Chapter 7
441