Allen-Bradley LOGIX 5000 Reference Manual page 209

Controllers advanced process control and drives and equipment phase and sequence instructions
Hide thumbs Also See for LOGIX 5000:
Table of Contents

Advertisement

Process Control Instructions
Input Parameters Data
Type
CV2Prog
REAL
CV3Prog
REAL
CV1Oper
REAL
CV2Oper
REAL
CV3Oper
REAL
CV1OverrideValue
REAL
CV2OverrideValue
REAL
Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
Description
CV2 Program-Manual value. CV2 is set to this
value when in Program control and Manual
mode.
CV3 Program-Manual value. CV3 is set to this
value when in Program control and Manual
mode.
CV1 Operator-Manual value.
• CV1 is set to this value when in Operator
control and Manual mode. If not Operator-
Manual mode, set CV1Oper to the value of CV1
at the end of each function block execution.
• If value of CV1Prog or CV1Oper < 0 or > 100,
or < CV1LLimit or > CV1HLimit when
CVManLimiting is TRUE, set unique Status bit
and limit value used for CV1.
CV2 Operator-Manual value.
• CV2 is set to this value when in Operator
control and Manual mode. If not Operator-
Manual mode, set CV2Oper to the value of CV2
at the end of each function block execution.
• If value of CV2Prog or CV2Oper < 0 or > 100,
or < CV2LLimit or > CV2HLimit when
CVManLimiting is TRUE, set unique Status bit
and limit value used for CV2.
CV3 Operator-Manual value.
• CV3 is set to this value when in Operator
control and Manual mode. If not Operator-
Manual mode, set CV3Oper to the value of CV3
at the end of each function block execution.
• If value of CV3Prog or CV3Oper < 0 or > 100,
or < CV3LLimit or > CV3HLimit when
CVManLimiting is TRUE, set unique Status bit
and limit value used for CV3.
CV1 Override value.
• CV1 set to this value when in Override mode.
This value should correspond to a safe state
output of the loop.
• If value of CV1OverrideValue < 0 or >100, set
unique Status bit and limit value used for CV1.
CV2 Override value.
• CV2 set to this value when in Override mode.
This value should correspond to a safe state
output of the loop.
• If value of CV2OverrideValue < 0 or >100, set
unique Status bit and limit value used for CV2.
Chapter 1
Values
Valid = 0.0 through 100.0
Default = 0.0
Valid = 0.0 through 100.0
Default = 0.0
Valid = 0.0 through 100.0
Default = 0.0
Valid = 0.0 through 100.0
Default = 0.0
Valid = 0.0 through 100.0
Default = 0.0
Valid = 0.0 through 100.0
Default = 0.0
Valid = 0.0 through 100.0
Default = 0.0
209