LowInCutoff
REAL
ProgProgReq
BOOL
ProgOperReq
BOOL
ProgStartReq
BOOL
ProgStopReq
BOOL
ProgResetReq
BOOL
OperProgReq
BOOL
OperOperReq
BOOL
OperStartReq
BOOL
OperStopReq
BOOL
OperResetReq
BOOL
ProgValueReset
BOOL
Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
The instruction low input cutoff input. When the
In is at or below the LowInCutoff value,
totalization ceases.
Valid = any float
Default = 0.0
Program program request. Set to true to request
Program control. Ignored if ProgOperReq is true.
Holding this true and ProgOperReq false locks
the instruction in Program control.
Default is false.
Program operator request. Set to true to request
Operator control. Holding this true locks the
instruction in Operator control.
Default is false.
The program start request input. Set to true to
request totalization to start.
Default is false.
The program stop request input. Set to true to
request totalization to stop.
Default is false.
The program reset request input. Set to true to
request the Total to reset to the ResetValue.
Default is false.
Operator program request. Set to true by the
operator interface to request Program control.
The instruction clears this input to false.
Default is false.
Operator operator request. Set to true by the
operator interface to request Operator control.
The instruction clears this input to false.
Default is false.
The operator start request input. Set to true by
the operator interface to request totalization to
start. The instruction clears this input to false.
Default is false.
The operator stop request input. Set to true by
the operator interface to request totalization to
stop. The instruction clears this input to false.
Default is false.
The operator reset request input. Set to true by
the operator interface to request totalization to
reset. The instruction clears this input to false.
Default is false.
Reset program control values. When true, clear
all the program request inputs to false at each
execution of the instruction.
Default is false.