Allen-Bradley LOGIX 5000 Reference Manual page 152

Controllers advanced process control and drives and equipment phase and sequence instructions
Hide thumbs Also See for LOGIX 5000:
Table of Contents

Advertisement

Chapter 1
Process Control Instructions
152
CV2Oper
REAL
CV3Oper
REAL
CV1OverrideValue
REAL
CV2OverrideValue
REAL
CV3OverrideValue
REAL
Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
CV2 Operator-Manual value. CV2 is set
to this value when in Operator control
and Manual mode. If not Operator-
Manual mode, set CV2Oper to the
value of CV2 at the end of each
function block execution.
If value of CV2Oper < 0 or > 100, or <
CV2LLimit or > CV2HLimit when
CVManLimiting is TRUE, set unique
Status bit and limit value used for CV.
CV3 Operator-Manual value. CV3 is set
to this value when in Operator control
and Manual mode. If not Operator-
Manual mode, set CV3Oper to the
value of CV3 at the end of each
function block execution.
If value of CV3Oper < 0 or > 100, or <
CV3LLimit or > CV3HLimit when
CVManLimiting is TRUE, set unique
Status bit and limit value used for CV.
CV1 Override value. CV1 set to this
value when in Override mode.
This value should correspond to a safe
state output of the loop.
If value of CV1OverrideValue < 0 or
>100, set unique Status bit and limit
value used for CV.
CV2 Override value. CV2 set to this
value when in Override mode.
This value should correspond to a safe
state output of the loop.
If value of CV2OverrideValue < 0 or
>100, set unique Status bit and limit
value used for CV.
CV3 Override value. CV3 set to this
value when in Override mode.
This value should correspond to a safe
state output of the loop.
If value of CV3OverrideValue < 0 or
>100, set unique Status bit and limit
value used for CV.
Valid = 0.0...100.0
Default = 0.0
Valid = 0.0...100.0
Default = 0.0
Valid = 0.0...100.0
Default = 0.0
Valid = 0.0...100.0
Default = 0.0
Valid = 0.0...100.0
Default = 0.0