Allen-Bradley LOGIX 5000 Reference Manual page 309

Controllers advanced process control and drives and equipment phase and sequence instructions
Hide thumbs Also See for LOGIX 5000:
Table of Contents

Advertisement

Drives
UPDN Structure
Input Parameter
EnableIn
Initialize
InitialValue
InPlus
InMinus
Hold
Output Parameter
EnableOut
Out
Structured Text
Operand
Type
UPDN tag
UP_DOWN_ACCUM
See Structured Text Syntax for more information of the syntax of expressions
within structured text.
Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
Data Type
Description
BOOL
Enable input. If cleared, the instruction
does not execute and outputs are not
updated.
Default is set.
BOOL
The initialize input request for the
instruction. When Initialize is set, the
instruction sets Out and the internal
accumulator to InitialValue.
Default is cleared.
REAL
The initialize value of the instruction.
Valid = any float
Default = 0.0
REAL
The input added to the accumulator.
Valid = any float
Default = 0.0
REAL
The input subtracted from the
accumulator.
Valid = any float
Default = 0.0
BOOL
The hold input request for the
instruction. When Hold is set and
Initialize is cleared, Out is held.
Default is cleared.
Data Type
Description
BOOL
Indicates if instruction is enabled.
Cleared to false if Out overflows.
REAL
The output of the instruction.
Format
Description
Structure
UPDN structure