Allen-Bradley LOGIX 5000 Reference Manual page 29

Controllers advanced process control and drives and equipment phase and sequence instructions
Hide thumbs Also See for LOGIX 5000:
Table of Contents

Advertisement

Process Control Instructions
Input Parameter
Data
Type
HandFB1
BOOL
HandFB2
BOOL
FaultTime
REAL
FaultAlarmLatch
BOOL
FaultAlmUnLatch
BOOL
OverrideOnInit
BOOL
OverrideOnFault
BOOL
Out0State0
BOOL
Out0State1
BOOL
Out0State2
BOOL
Out1State0
BOOL
Out1State1
BOOL
Out1State2
BOOL
Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
Description
Hand feedback state 1. This input from a field hand/off/auto station shows the
requested state of the field device. True indicates the field device is being
requested to enter the 1 state; false indicates the field device is being requested to
enter some other state.
Default is false.
Hand feedback state 2. This input from a field hand/off/auto station shows the
requested state of the field device. True indicates the field device is being
requested to enter the 2 state; false indicates the field device is being requested to
enter some other state.
Default is false.
Fault time value. Configure the value in seconds of the time to allow the device to
reach a newly commanded state. Set FaultTime = 0 to disable the fault timer. If
this value is invalid, the instruction assumes a value of zero and sets the
appropriate bit in Status.
Valid = any float
0.0
Default = 0.0
Fault alarm latch input. When true and FaultAlarm is true, latch FaultAlarm. To
unlatch FaultAlarm, set FaultAlmUnlatch to true or clear FaultAlarmLatch to false.
Default is false.
Fault alarm unlatch input. Set this input to true when FaultAlarmLatch is set to
unlatch FaultAlarm. The instruction clears this input to false.
Default is false.
Override on initialization request. If this bit is true, then during instruction first
scan, the instruction is placed in Operator control with Override true and Hand
false. If ProgHandReq is true, then Override is cleared to false and Hand is set to
true.
Default is false.
Override on fault request. Set this value to true if the device should go to Override
mode and enter the Override State on a fault alarm. After the fault alarm is
removed, the instruction is placed in Operator control.
Default is false.
Output 0 state 0 input. This value determines the value of Output0 when the
device is in the 0 state.
Default is false.
Output 0 state 1 input. This value determines the value of Output0 when the
device is in the 1 state.
Default is false.
Output 0 state 2 input. This value determines the value of Output0 when the
device is in the 2 state.
Default is false.
Output 1 state 0 input. This value determines the value of Output1 when the
device is in the 0 state.
Default is false.
Output 1 state 1 input. This value determines the value of Output1 when the
device is in the 1 state.
Default is false.
Output 1 state 2 input. This value determines the value of Output1 when the
device is in the 2 state.
Default is false.
Chapter 1
29