Process Control Instructions
Input Parameters Data
Type
CV2PV1ResponseSp
DINT
eed
CV3PV1ResponseSp
DINT
eed
CV1PV2ResponseSp
DINT
eed
CV2PV2ResponseSp
DINT
eed
CV3PV2ResponseSp
DINT
eed
CV1PV1ModelInit
BOOL
CV2PV1ModelInit
BOOL
CV3PV1ModelInit
BOOL
Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
Description
Desired speed of closed loop response for CV2
PV1.
• Slow response: ResponseSpeed=0
• Medium response: ResponseSpeed=1
• Fast response: ResponseSpeed=2
If ResponseSpeed is less than 0, Slow response is
used. If ResponseSpeed is greater than 2, Fast
response is used.
Desired speed of closed loop response for CV3
PV1.
• Slow response: ResponseSpeed=0
• Medium response: ResponseSpeed=1
• Fast response: ResponseSpeed=2
If ResponseSpeed is less than 0, Slow response is
used. If ResponseSpeed is greater than 2, Fast
response is used.
Desired speed of closed loop response for CV1
PV2.
• Slow response: ResponseSpeed=0
• Medium response: ResponseSpeed=1
• Fast response: ResponseSpeed=2
If ResponseSpeed is less than 0, Slow response is
used. If ResponseSpeed is greater than 2, Fast
response is used.
Desired speed of closed loop response for CV2
PV2.
• Slow response: ResponseSpeed=0
• Medium response: ResponseSpeed=1
• Fast response: ResponseSpeed=2
If ResponseSpeed is less than 0, Slow response is
used. If ResponseSpeed is greater than 2, Fast
response is used.
Desired speed of closed loop response for CV3
PV2.
• Slow response: ResponseSpeed=0
• Medium response: ResponseSpeed=1
• Fast response: ResponseSpeed=2
If ResponseSpeed is less than 0, Slow response is
used. If ResponseSpeed is greater than 2, Fast
response is used.
Internal model initialization switch for CV1 - PV1.
Refer to Function Block Attributes.
Internal model initialization switch for CV2 - PV1.
Refer to Function Block Attributes.
Internal model initialization switch for CV3 - PV1.
Refer to Function Block Attributes.
Chapter 1
Values
Range: 0...2
Default=1
Range: 0 through 2
Default=1
Range: 0 through 2
Default=1
Range: 0 through 2
Default=1
Range: 0 through 2
Default=1
Default = FALSE
Default = FALSE
Default = FALSE
221