Process Control Instructions
Output
Data
Parameters
Type
AtuneCV1PV2Chan
BOOL
ged
AtuneCV2PV2Chan
BOOL
ged
AtuneCV3PV2Chan
BOOL
ged
AtuneCV1PV2Time
BOOL
out
AtuneCV2PV2Time
BOOL
out
AtuneCV3PV2Time
BOOL
out
AtuneCV1PV2NotS
BOOL
ettled
AtuneCV2PV2NotS
BOOL
ettled
AtuneCV3PV2NotS
BOOL
ettled
Status1
DINT
Status2
DINT
Status3CV1
DINT
Status3CV2
DINT
Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
Description
CV1Oper is changed when in Operator control or
CV1Prog is changed when in Program control or
CV1 becomes high/low or ROC limited during CV1 -
PV2 Autotuning. When True, CV1 - PV2 Autotuning
is aborted.
CV2Oper is changed when in Operator control or
CV2Prog is changed when in Program control or
CV2 becomes high/low or ROC limited during CV2 -
PV2 Autotuning. When True, CV2 - PV2 Autotuning
is aborted.
CV3Oper is changed when in Operator control or
CV3Prog is changed when in Program control or
CV3 becomes high/low or ROC limited during CV3 -
PV2 Autotuning. When True, CV3 - PV2 Autotuning
is aborted.
Elapsed time is greater then PV2AtuneTimeLimit
since step test is started. When True, CV1 - PV2
Autotuning is aborted.
Elapsed time is greater then PV2AtuneTimeLimit
since step test is started. When True, CV2 - PV2
Autotuning is aborted.
Elapsed time is greater then PV2AtuneTimeLimit
since step test is started. When True, CV3 - PV2
Autotuning is aborted.
The PV2 is changed too much to Autotune for CV1-
PV2. When True, CV1-PV2 Autotuning is aborted.
Wait until PV2 is more stable before autotuning
CV1-PV2.
The PV2 is changed too much to Autotune for CV2-
PV2. When True, CV2-PV2 Autotuning is aborted.
Wait until PV2 is more stable before autotuning
CV2-PV2.
The PV2 is changed too much to Autotune for CV3-
PV2. When True, CV3-PV2 Autotuning is aborted.
Wait until PV2 is more stable before autotuning
CV3-PV2.
Bit mapped status of the function block. A value of
0 indicates that no faults have occurred. Any
parameter that could be configured with an invalid
value must have a status parameter bit to indicate
its invalid status.
Additional bit mapped status for the function block.
A value of 0 indicates that no faults have occurred.
Any parameter that could be configured with an
invalid value must have a status parameter bit to
indicate its invalid status.
Additional bit mapped CV1 status for the function
block. A value of 0 indicates that no faults have
occurred.
Additional bit mapped CV2 status for the function
block. A value of 0 indicates that no faults have
occurred.
Chapter 1
Values
Bit 8 of AtuneCV1PV2Status
Bit 8 of AtuneCV2PV2Status
Bit 8 of AtuneCV3PV2Status
Bit 9 of AtuneCV1PV2Status
Bit 9 of AtuneCV2PV2Status
Bit 9 of AtuneCV3PV2Status
Bit 10 of AtuneCV1PV2Status
Bit 10 of AtuneCV2PV2Status
Bit 10 of AtuneCV3PV2Status
235