Allen-Bradley LOGIX 5000 Reference Manual page 363

Controllers advanced process control and drives and equipment phase and sequence instructions
Hide thumbs Also See for LOGIX 5000:
Table of Contents

Advertisement

Select_Limit Instructions
MUX Structure
Input Parameter
Data Type
EnableIn
BOOL
In1
REAL
In2
REAL
In3
REAL
In4
REAL
In5
REAL
In6
REAL
In7
REAL
In8
REAL
Selector
DINT
Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
Description
Enable input. If cleared, the instruction does
not execute and outputs are not updated.
Default is set.
The first analog signal input to the
instruction.
Valid = any float
Default = 0.0
The second analog signal input to the
instruction.
Valid = any float
Default = 0.0
The third analog signal input to the
instruction.
Valid = any float
Default = 0.0
The fourth analog signal input to the
instruction.
Valid = any float
Default = 0.0
The fifth analog signal input to the
instruction.
Valid = any float
Default = 0.0
The sixth analog signal input to the
instruction.
Valid = any float
Default = 0.0
The seventh analog signal input to the
instruction.
Valid = any float
Default = 0.0
The eighth analog signal input to the
instruction.
Valid = any float
Default = 0.0
The selector input to the instruction. This
input determines which of the inputs (1-8) is
moved into Out. If this value is invalid (which
includes 0), the instruction sets the
appropriate bit in Status and holds Out at its
current value.
Valid = 1 to 8
Default = 0
Chapter 4
363