Process Control Instructions
Input Parameters Data
Type
OperProgReq
BOOL
OperOperReq
BOOL
OperCV1AutoReq
BOOL
OperCV2AutoReq
BOOL
OperCV3AutoReq
BOOL
OperCV1ManualReq BOOL
OperCV2ManualReq BOOL
OperCV3ManualReq BOOL
ProgValueReset
BOOL
TimingMode
DINT
OverSampleDT
REAL
Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
Description
Operator Program Request.
• Set TRUE by the operator interface to request
Program control. The function block resets this
parameter to FALSE.
Operator Operator Request.
• Set TRUE by the operator interface to request
Operator control. The function block resets this
parameter to FALSE.
Operator-Auto mode request for CV1.
Set TRUE by the operator interface to request
Auto mode. The function block resets this
parameter to FALSE.
Operator-Auto mode request for CV2.
Set TRUE by the operator interface to request
Auto mode. The function block resets this
parameter to FALSE.
Operator-Auto mode request for CV3.
Set TRUE by the operator interface to request
Auto mode. The function block resets this
parameter to FALSE.
Operator-Manual mode request for CV1.
Set TRUE by the operator interface to request
Manual mode. The function block sets this
parameter to FALSE.
Operator-Manual mode request for CV2.
Set TRUE by the operator interface to request
Manual mode. The function block sets this
parameter to FALSE.
Operator-Manual mode request for CV3.
Set TRUE by the operator interface to request
Manual mode. The function block sets this
parameter to FALSE.
Reset Program control values.
When TRUE, the Prog_xxx_Req inputs are reset
to FALSE. When TRUE and Program control, set
SP(x)Prog = SP(x) and CV(y)Prog = CV(y), where
x = 1,2 and y = 1,2,3
Selects Time Base Execution mode.
Value/Description
0 = Periodic mode
1 = Oversample mode
2 = Real time sampling mode
For more information about timing modes, see
Function Block Attributes.
Execution time for Oversample mode.
Chapter 1
Values
Default = FALSE
Default = FALSE
Default = FALSE
Default = FALSE
Default = FALSE
Default = FALSE
Default = FALSE
Default = FALSE
Default = FALSE
Valid = 0 through 2
Default = 0
Valid = 0 to max. TON_Timer
elapsed time (4194.303
seconds)
Default = 0