Process Control Instructions
38
Override
Override State
true
2
true
1
true
0
If OverrideState is invalid, the instruction sets the appropriate bit in Status and
does not enter the override state.
When Hand is true, it takes precedence over Program and Operator control. The
following table describes how the Hand mode affects the commanded state.
Hand
HandFB0
HandFB1
true
false
false
true
false
true
true
true
false
If more than one HandFB input is true, the instruction sets the appropriate bit in
Status and, if Hand is true, the instruction holds the previous state.
Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
Description
Command0Status is cleared to false
Command1Status is cleared to false
Command2Status is set to true
Command0Status is cleared to false
Command1Status is set to true
Command2Status is cleared to false
Command0Status is set to true
Command1Status is cleared to false
Command2Status is cleared to false
HandFB2
Description
true
Command0Status is cleared to false
Command1Status is cleared to false
Command2Status is set to true
false
Command0Status is cleared to false
Command1Status is set to true
Command2Status is cleared to false
false
Command0Status is set to true
Command1Status is cleared to false
Command2Status is cleared to false