Input Parameters Data
Type
CV1PV2ModelDT
REAL
CV2PV2ModelDT
REAL
CV3PV2ModelDT
REAL
CV1PV1RespTC
REAL
CV2PV1RespTC
REAL
CV3PV1RespTC
REAL
CV1PV2RespTC
REAL
CV2PV2RespTC
REAL
CV3PV2RespTC
REAL
PV1Act1stCV
DINT
PV1Act2ndCV
DINT
PV1Act3rdCV
DINT
PV2Act1stCV
DINT
PV2Act2ndCV
DINT
PV2Act3rdCV
DINT
TargetCV
DINT
Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
Description
The internal model deadtime for CV1 - PV2 in
seconds.
The internal model deadtime for CV2 - PV2 in
seconds.
The internal model deadtime for CV3 - PV2 in
seconds.
The tuning parameter that determines the speed
of the control variable action for CV1 - PV1 in
seconds.
The tuning parameter that determines the speed
of the control variable action for CV2 - PV1 in
seconds.
The tuning parameter that determines the speed
of the control variable action for CV3 - PV1 in
seconds.
The tuning parameter that determines the speed
of the control variable action for CV1 - PV2 in
seconds.
The tuning parameter that determines the speed
of the control variable action for CV2 - PV2 in
seconds.
The tuning parameter that determines the speed
of the control variable action for CV3 - PV2 in
seconds.
The first CV to act to compensate for PV1-SP1
deviation.
1=CV1, 2=CV2, 3=CV3
The second CV to act to compensate for PV1-SP1
deviation.
1=CV1, 2=CV2, 3=CV3
The third CV to act to compensate for PV1-SP1
deviation.
1=CV1, 2=CV2, 3=CV3
The first CV to act to compensate for PV2-SP2
deviation.
1=CV1, 2=CV2, 3=CV3
The second CV to act to compensate for PV2-SP2
deviation.
1=CV1, 2=CV2, 3=CV3
The third CV to act to compensate for PV2-SP2
deviation.
1=CV1, 2=CV2, 3=CV3
The CV to be driven to its target value.
1=CV1, 2=CV2, 3=CV3
Values
Valid = 0.0 to maximum
positive float
Default = 0.0
Valid = 0.0 to maximum
positive float
Default = 0.0
Valid = 0.0 to maximum
positive float
Default = 0.0
Valid = 0.0 to maximum
positive float
Default = 0.0
Valid = 0.0 to maximum
positive float
Default = 0.0
Valid = 0.0 to maximum
positive float
Default = 0.0
Valid = 0.0 to maximum
positive float
Default = 0.0
Valid = 0.0 to maximum
positive float
Default = 0.0
Valid = 0.0 to maximum
positive float
Default = 0.0
Valid = 1-3
Default = 1
Valid = 1-3
Default = 2
Valid = 1-3
Default = 3
Valid = 1-3
Default = 1
Valid = 1-3
Default = 2
Valid = 1-3
Default = 3
Valid = 1-3
Default = 3