3.3.2 Lifting

Lift the adjustable frequency drive using the dedicated
lifting eyes. For all D-frames, use a bar to avoid bending
the lifting holes of the adjustable frequency drive.
152.8 210.8
(Pa)
Figure 3.5 Recommended Lifting Method, Frame Size D13
Figure 3.6 Recommended Lifting Method, Frame Size E9
WARNING
200
225
The lifting bar must be able to handle the weight of the
adjustable frequency drive. See chapter 11.2.1 Mechanical
Dimensions for the weight of the different frame sizes.
Maximum diameter for bar is 1 in [2.5 cm]. The angle
from the top of the adjustable frequency drive to the
lifting cable should be 60° or greater.