Application Examples
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
7
7
A OUT
42
COM
39
U - I
A53
Table 7.4 Analog Speed Reference (Current)
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 7.5 Start/Stop Command with Safe Torque Off
120
Instruction Manual
Parameters
Function
Setting
6-12 Terminal 53
4 mA*
Low Current
6-13 Terminal 53
20 mA*
High Current
6-14 Terminal 53
0 RPM
Low Ref./Feedb.
Value
6-15 Terminal 53
1,500 RPM
High Ref./Feedb.
Value
*=Default Value
+
Notes/comments:
-
4 - 20mA
Parameters
Function
Setting
5-10 Terminal 18
[8] Start*
Digital Input
5-12 Terminal 27
[0] No
Digital Input
operation
5-19 Terminal 37
[1] Safe Stop
Safe Stop
Alarm
*=Default Value
Notes/comments:
If 5-12 Terminal 27 Digital Input
is set to [0] No operation, a
jumper wire to terminal 27 is
not needed.
Danfoss A/S © Rev. 2014-02-07 All rights reserved.
Speed
Start (18)
Figure 7.1 Start/Stop with Safe Torque Off
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 7.6 Pulse Start/Stop
Speed
Latched Start (18)
Stop Inverse (27)
Figure 7.2 Latched Start/Stop Inverse
Parameters
Function
Setting
5-10 Terminal 18
[9] Latched
Digital Input
Start
5-12 Terminal 27
[6] Stop
Digital Input
Inverse
*=Default Value
Notes/comments:
If 5-12 Terminal 27 Digital Input
is set to [0] No operation, a