Local Control Test - Danfoss VLT AutomationDrive FC 302 Instruction Manual

Low harmonic drive 132–630 kw
Hide thumbs Also See for VLT AutomationDrive FC 302:
Table of Contents

Advertisement

Start-up and Functional Tes...
4.
Press the navigation keys to scroll to parameter
group 0-0* Basic Settings and press [OK].
4
4
Figure 4.2 0-0* Basic Settings
5.
Press the navigation keys to scroll to
0-03 Regional Settings and press [OK].
Figure 4.3 0-03 Regional Settings
6.
Press the navigation keys to select International
or North America as appropriate and press [OK].
(This changes the default settings for a number
of basic parameters. See chapter 6 Programming
for a complete list.)
7.
Press [Quick Menu] on the LCP.
8.
Press the navigation keys to scroll to parameter
group Q2 Quick Set-up.
9.
Press [OK].
Figure 4.4 Q2 Quick Set-up
42
Instruction Manual
0.0%
0.00A
Operation / Display
0-0
*
Basic Settings
0-1
Set-up Operations
*
0-2
*
LCP Display
0-3
*
LCP Custom Readout
0.0%
0.00A
Basic Settings
0-03 Regional Settings
[0] International
13.7%
13.0A
Quick Menus
Q1 My Personal Menu
Q2 Quick Setup
Q5 Changes Made
Q6 Loggings
Danfoss A/S © Rev. 2014-02-07 All rights reserved.
10.
Select language and press [OK].
1(1)
0-
**
Figure 4.5 Select Language
11.
If a jumper wire is placed between control
terminals 12 and 27 leave 5-12 Terminal 27 Digital
Input at factory default. Otherwise select No
Operation. For adjustable frequency drives with
an optional bypass, no jumper wire is required.
1(1)
0-0
*
12.
parameter 3-02 Minimum Reference
13.
parameter 3-03 Maximum Reference
14.
3-41 Ramp 1 Ramp-up Time
15.
3-42 Ramp 1 Ramp-down Time
16.
3-13 Reference Site. Linked to Hand/Auto* Local
Remote.

4.4 Local Control Test

CAUTION
MOTOR START!
Ensure that the motor, system and any attached
equipment are ready for start. It is the responsibility of
the user to ensure safe operation under any condition.
Failure to ensure that the motor, system, and any
attached equipment are ready for start could result in
personal injury or equipment damage.
NOTICE!
1(1)
The [Hand On] key provides a local start command to
the adjustable frequency drive. The [Off] key provides
the stop function.
When operating in local mode, [
decrease the speed output of the adjustable frequency
drive. [◄] and [►] move the display cursor in the numeric
display.
0.0 Hz
0.00kW
Motor Setup
1 - 21 Motor Power [kW]
4.0
kW
] and [
] increase and
1(1)
Q2
MG37A222