Power Rating - Danfoss VLT AutomationDrive FC 302 Instruction Manual

Low harmonic drive 132–630 kw
Hide thumbs Also See for VLT AutomationDrive FC 302:
Table of Contents

Advertisement

Specifications

11.4.1 Power Rating

Grid conditions
Supply voltage
AC line voltage low/line drop-out:
During low AC line voltage or a line drop-out, the filter continues until the intermediate circuit voltage drops below the
minimum stop level, which corresponds to 15% below the filter lowest rated supply voltage. Full compensation cannot be
expected at AC line voltage lower than 10% below the filter lowest rated supply voltage. If AC line voltage exceeds the filter
highest rated voltage, the filter continues to work but harmonic mitigation performance is reduced. The filter does not cut out
until AC line voltages exceed 580 V.
Supply frequency
Max. imbalance temporary between line phases
where mitigation performance is kept high.
Max THDv pre-distortion
Harmonic mitigation performance
THiD
Individual harmonic mitigation ability:
2nd
4th
5th
7th
8th
10th
11th
13th
14th
16th
17th
19th
20th
22nd
23rd
25th
Total current of harmonics
The filter is performance tested to the 40th order
Reactive current compensation
Cos phi
Reactive current, % of filter current rating
MG37A222
Instruction Manual
Filter mitigates at higher line imbalance but harmonic mitigation
Reduced performance for higher pre-distortion levels
Danfoss A/S © Rev. 2014-02-07 All rights reserved.
3.0% of rated supply voltage
performance is reduced
10% with kept mitigation performance
Best performance <4%
Depending on filter vs. distortion ratio.
Current maximum RMS [% of rated RMS current]
Controllable 1.0 to 0.5 lagging
380–480 V
50/60 Hz ±5%
10%
10%
70%
50%
10%
5%
11
11
32%
28%
4%
4%
20%
18%
3%
3%
16%
14%
90%
100%
161