Warning And Alarm Definitions - Filter (Left Lcp) - Danfoss VLT AutomationDrive FC 302 Instruction Manual

Low harmonic drive 132–630 kw
Hide thumbs Also See for VLT AutomationDrive FC 302:
Table of Contents

Advertisement

Warnings and Alarms

9.5 Warning and Alarm Definitions - Filter (Left LCP)

NOTICE!
This section covers warnings and alarms on the filter side LCP. For warning and alarms for the adjustable frequency
drive, see chapter 9.4 Warnings and Alarm Definitions - Adjustable Frequency Drive
A warning or an alarm is signaled by the relevant LED on the front of the filter and indicated by a code on the display.
A warning remains active until its cause is no longer present. Under certain circumstances, operation of the unit may still be
continued. Warning messages may be critical, but are not necessarily so.
In the event of an alarm, the unit will have tripped. Alarms must be reset to restart operation once their cause has been
rectified.
This may be done in four ways:
1.
By pressing [Reset].
2.
Via a digital input with the "Reset" function.
3.
Via serial communication/optional serial communication bus.
4.
By resetting automatically using the [Auto Reset] function.
NOTICE!
After a manual reset pressing [Reset], press [Auto On] or [Hand On] to restart the unit.
If an alarm cannot be reset, the reason may be that its cause has not been rectified, or the alarm is trip-locked (see also
Table 9.3).
Alarms that are trip-locked offer additional protection, meaning that the line power supply must be switched off before the
alarm can be reset. After being switched back on, the unit is no longer blocked and may be reset as described above once
the cause has been rectified.
Alarms that are not trip-locked can also be reset using the automatic reset function in 14-20 Reset Mode (Warning: automatic
wake-up is possible)
If a warning and alarm is marked against a code in Table 9.3, either a warning occurs before an alarm, or it can be specified
whether it is a warning or an alarm that is to be displayed for a given fault.
MG37A222
Instruction Manual
Danfoss A/S © Rev. 2014-02-07 All rights reserved.
9
9
139

Advertisement

Table of Contents
loading

Table of Contents