Danfoss VLT AutomationDrive FC 302 Instruction Manual page 144

Low harmonic drive 132–630 kw
Hide thumbs Also See for VLT AutomationDrive FC 302:
Table of Contents

Advertisement

Warnings and Alarms
Alarm Word and Extended Status Word
Bit
Hex
0
00000001
1
00000002
2
00000004
3
00000008
4
00000010
5
00000020
6
00000040
7
00000080
8
00000100
9
00000200
10
00000400
11
00000800
12
00001000
13
00002000
14
00004000
15
00008000
16
00010000
17
00020000
18
00040000
9
9
19
00080000
20
00100000
21
00200000
22
00400000
23
00800000
24
01000000
25
02000000
26
04000000
27
08000000
28
10000000
29
20000000
30
40000000
31
80000000
Table 9.5 Description of Alarm Word, Warning Word and Extended Status Word
The alarm words, warning words and extended status words can be read out via serial bus or optional serial communication
bus for diagnosis. See also 16-90 Alarm Word, 16-92 Warning Word and 16-94 Ext. Status Word. "Reserved" means that the bit
is not guaranteed to be any particular value. Reserved bits should not be used for any purpose.
142
Instruction Manual
Dec
Alarm Word
1
Mains cont. fault
2
Heatsink temp
4
Ground fault
8
Ctrl.card temp
16
Ctrl. word TO
32
Overcurrent
64
SC cont. fault
128
Cap. overcurrent
256
Cap. ground fault
512
Inverter overld.
1024
DC under volt
2048
DC overvolt
4096
Short-circuit
8192
Inrush fault
16384
Mains ph. loss
32768
Auto CT error
65536
Reserved
131072
Internal fault
262144
DC overcurrent
524288
Resistor temp
1048576
Power ground fault
2097152
Switch. freq. limit
4194304
Fieldbus fault
8388608
24 V supply low
16777216
CT range
33554432
1.8 V supply low
67108864
Reserved
134217728
Auto CT interrupt
268435456
Option change
536870912
Unit initialized
1073741824
Safe torque off
2147483648
Mains freq. limit
Danfoss A/S © Rev. 2014-02-07 All rights reserved.
Warning Word
Reserved
Heatsink temp
Ground fault
Ctrl.card temp
Ctrl. word TO
Overcurrent
Reserved
Cap. overcurrent
Cap. ground fault
Inverter overld.
DC under volt
DC overvolt
DC voltage low
DC voltage high
Mains ph. loss
Reserved
Reserved
10 V low
DC overcurrent
Resistor temp
Power ground fault
Reserved
Fieldbus fault
24 V supply low
Reserved
Reserved
Low temp
Reserved
Reserved
Unit initialized
Safe torque off
Extended status word
Extended Status Word
Reserved
Auto CT running
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Password Time Lock
Password Protection
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved