Line Power Disconnects; F-Frame Circuit Breakers; F-Frame Line Power Contactors; Motor Insulation - Danfoss VLT AutomationDrive FC 302 Instruction Manual

Low harmonic drive 132–630 kw
Hide thumbs Also See for VLT AutomationDrive FC 302:
Table of Contents

Advertisement

Installation

3.4.12 Line Power Disconnects

Frame size
D
3
3
E
E
F
F
Table 3.9 Recommended Line Power Disconnects

3.4.13 F-Frame Circuit Breakers

Frame size
F
F
Table 3.10 Recommended Circuit Breakers

3.4.14 F-Frame Line Power Contactors

Frame size
F
F
Table 3.11 Recommended Contactors

3.4.15 Motor Insulation

For motor cable lengths ≤ the maximum cable length, the motor insulation ratings listed in Table 3.12 are recommended.
The peak voltage can be twice the DC link voltage or 2.8 times AC line voltage, due to transmission line effects in the motor
cable. If a motor has lower insulation rating, use a dU/dt or sine-wave filter.
Table 3.12 Recommended Motor Insulation Ratings
30
Instruction Manual
Power & Voltage
P132–P200 380–500 V
P250 380–500 V
P315–P400 380–500 V
P450 380–500 V
P500–P630 380–500 V
Power & Voltage
P450 380–500 V
P500–P630 380–500 V
Power & Voltage
P450–P500 380–500 V
P560–P630 380–500 V
Nominal AC Line Voltage
≤ 420 V
U
N
420 V < U
≤ 500 V
N
Danfoss A/S © Rev. 2014-02-07 All rights reserved.
Type
OT400U12-9 or ABB OETL-NF400A
ABB OETL-NF600A
ABB OETL-NF800A
Merlin Gerin NPJF36000S12AAYP
Merlin Gerin NRK36000S20AAYP
Type
Merlin Gerin NPJF36120U31AABSCYP
Merlin Gerin NRJF36200U31AABSCYP
Type
Eaton XTCE650N22A
Eaton XTCEC14P22B
Motor Insulation
Standard U
= 1,300 V
LL
Reinforced U
= 1,600 V
LL