Safety

1 Safety
1.1 Safety
WARNING
HIGH VOLTAGE
Adjustable frequency drives contain high voltage when
connected to AC line input power. Qualified personnel
only should perform installation, start-up, and
maintenance. Failure to have qualified personnel
perform installation, start-up, and maintenance could
result in death or serious injury.
WARNING
UNINTENDED START
When the adjustable frequency drive is connected to AC
line power, the motor may start at any time. The
adjustable frequency drive, motor, and any driven
equipment must be in operational readiness. Failure to
be in operational readiness when the adjustable
frequency drive is connected to AC line power could
result in death, serious injury, equipment, or property
damage.
MG37A222
Instruction Manual
WARNING
DISCHARGE TIME
Adjustable frequency drives contain DC link capacitors
that can remain charged even when the adjustable
frequency drive is not powered. To avoid electrical
hazards, disconnect AC line power, any permanent
magnet type motors, and any remote DC link power
supplies, including battery backups, UPS and DC link
connections to other adjustable frequency drives. Wait
for the capacitors to fully discharge before performing
any service or repair work. The wait time required is
listed in the Discharge Time table. Failure to wait the
specified time after power has been removed before
doing service or repair could result in death or serious
injury.
Voltage
[V]
380–500
Table 1.1 Discharge Times
*Power ranges are for normal overload operation.
Table 1.2 Approvals
Danfoss A/S © Rev. 2014-02-07 All rights reserved.
Power range
Minimum waiting time
(hp [kW])
175–350 [132–250 kW]*
425–850 [315–630 kW]
1
1
(min)
20
40
5