4. Diagnostics and error treatment
Error
Description and possible cause
No.
Configuration error (CPX error category 100)
1
CAN communication cannot be established
– Logic voltage of the actuator not
switched on.
– Cable defective.
– Wrong communication settings
(Profile: FHPP, Node ID, Baud rate).
– No terminating resistors.
2
Wrong axis type in the configuration
3
FHPP data profile not active
Execution error (CPX error category 101)
10
Axis is not referenced
11
Error when homing is started
– Internal drive error.
12
Error during homing
– Enable signal not set.
13
SW limit switch
– Internal software limit of end position
reached.
14
Neg. limit switch
– Neg. limit switch actuated.
15
Pos. limit switch
– Pos. limit switch actuated.
16
Positioning error
– Lag limit reached
– Controller parameters incorrect.
4-6
Error handling
Switch on the logic voltage of the
actuator
Replace cable
Correct settings
Install terminating resistors
Correct axis type
Correct communication profile
Carrying out homing
Contact Festo
Check control signals for homing.
Check controller parameters
Check software end position settings
Check neg. limit switch
Check pos. limit switch
Check controller parameters
Correct controller parameters