B. Ethernet/IP Objects of the CPX-FB32
B.4.3 Status and Diagnostic Object
Attr.
Access
Description
No.
1
Get
Status bits (8 bit)
Source of error: Bit 0: Valve
Error type:
2
Get
Number of the first module in which a fault has
occurred
3
Get
Diagnostic status
4
Get
Error number
5
Get/Set
Address I/O diagnostic interface
16 output bits (task data) of the I/O diagnostic
interface
6
Get
Data I/O diagnostic interface
16 input bits (reply data) of the I/O diagnostic
interface
Festo P.BE-CPX-FB32-EN en 1111a
Object class:
133
Instances:
1
The status bits and the I/O diagnostic interface are
mapped here.
Bit 1: Output
Bit 2: Input
Bit 3: Analogue/
technology module
Bit 4: Undervoltage
Bit 5: Short circuit/overload
Bit 6: Wire break
Bit 7: Other error
Type
Function
no.
BYTE
1936
BYTE
1937
BYTE
BYTE
1938
WORD
WORD
B-19