3. Diagnostics
NS – network status
LED
Sequence
ON
OFF
Is off
ON
OFF
Flashes green
ON
OFF
Lights up green
ON
OFF
Flashes red
ON
OFF
Lights up red
ON
OFF
Flashes red/green
*)
Test algorithm which ensures that no station numbers are assigned double in the network.
The test is usually carried out automatically when the network connection is set up.
Festo P.BE-CPX-FB32-EN en 1111a
Status
The CPX terminal is not
online
– Logic supply for bus
interface not applied
CPX terminal is online and
has received an IP address,
but the CPX terminal does
not have a configured
connection.
The CPX terminal is online
and has a connection to
the fieldbus
One or more
"I/O connections" are in
the time-out status
Communication has failed.
– Non-permitted IP
address set and already
used in the network
CPX terminal is in self-test
Meaning / error handling
• Check logic supply
• Check configuration; it is possible
that the CPX terminal is not
assigned to a master/scanner
or
• Check the status of the master, it
is possible that the master is not in
the RUN mode.
None (normal operating status)
Check the physical connection to the
master/scanner (EtherNet cable).
• Correct IP address
None