1. Installation
Tip
Settings
1-16
2. Set the network settings with the Handheld (CPX-MMI) or
the program "BOOTP-DHCP Server" from Rockwell
Automation. This activates saving of the network settings.
Fixed addressing via DIL switch
The fixed setting of the IP address is to be recommended for
test purposes during commissioning or for small networks.
If a (binary coded) number not equal to 0 or 255 is set with
the switch elements of DIL switch 3, the IP address is
assigned fixed. The set number specifies the host ID of the
address "192.168.1.xxx" (see Fig. 1/4).
Example: Set IP address:
192.168.1.005
Fig. 1/4: Examples of set IP addresses (binary coded) with
fixed addressing
In case of fixed addressing, the setting of the network mask
and the gateway are set unchangeably to:
Network mask:
255.255.255.0
Gateway:
0.0.0.0
Example: Set IP address:
192.168.1.038
0
2
2
+ 2
=
1 + 4 =
5
Festo P.BE-CPX-FB32-EN en 1111a
1
2
5
2
+ 2
+ 2
=
2 + 4 + 32 =
38