Festo CPX-FB32 Manual page 116

Cpx terminal, cpx field bus node, fieldbus protocol ethernet/ip
Hide thumbs Also See for CPX-FB32:
Table of Contents

Advertisement

B. Ethernet/IP Objects of the CPX-FB32
Attr.
Access
Description
No.
9
Get/Set
Monitoring (bit 0 ... 7)
Bit 0:
Bit 1:
Bit 2:
Bit 3:
Bit 4:
Bits 5 ... 7:reserved
1: active (presetting)
0: inactive
10
Get/Set
Fail safe
0: Reset all outputs (presetting)
1: Hold last state (Retain signal status)
2: Assume Fault mode
11
Get/Set
Force mode
0: blocked
1: enabled
12
Get/Set
System Idle mode
0: Reset all outputs (presetting)
1: Hold last state (Retain signal status)
2: Assume Idle mode
13
Get/Set
System start
0: System start with default parameterisation
(factory setting) and current CPX disassembly;
external parameterisation possible
(presetting)
1: System start with stored parameterisation
B-18
Monitoring SCS (short circuit/
overload sensor supply)
Monitoring SCO (short circuit/
overload outputs)
Monitoring Uout
(Undervoltage outputs)
Monitoring Uval
(Undervoltage valves)
Monitoring SCV
(short circuit valves)
and stored CPX expansion; Parameter and
CPX-expansion are stored remanently;
external parameterisation is blocked;
the M-LED on the fieldbus node is lit
Type
Function no.
BYTE
4401 (bit 0 ... 7)
BYTE
4402 (bit 0, 1)
BYTE
4402 (bit 2, 3)
BYTE
4402 (bit 4, 5)
BYTE
4402 (bit 6)
Festo P.BE-CPX-FB32-EN en 1111a