Status Bits - Festo CPX-E-PN Translation Of The Original Instructions

Bus module
Hide thumbs Also See for CPX-E-PN:
Table of Contents

Advertisement

Function
Maintenance/PROFIenergy [M/P]
LED
Meaning
(yel-
LED (yellow/green)
low/gr-
een)
No maintenance measures required, no
PROFIenergy activated
Off
Tab. 10 Maintenance/PROFIenergy [M/P]
Connection status [XF1], [XF2]
LED
Meaning
(green)
Network connection OK
Lights
up
Locating module if the LEDs XF1 and XF2
flash synchronously;
e.g.  for fault finding or during configuration
Flashes
No network connection
Off
Tab. 11 Connection Status [XF1], [XF2]
2.4.2

Status Bits

The system CPX-E provides 8 status bits for displaying global common diagnostic messages. The
status bits are configured like inputs and supply coded diagnostic information in the form of logic 0 or
logic 1. If all status bits supply a logic 0, there is no error. If, on the other hand, a status bit supplies a
logic 1, there is an error. In order to make use of the status bits function, the bus module of the
system CPX-E must be configured accordingly.
The status bits are shown in the process image if this has been specified by selecting the catalogue
entry "E-PN [Status]" in the hardware configurator.
If different errors occur simultaneously on different module types, errors cannot be assigned. To
clearly determine errors, the I/O diagnostic interface can be used è 2.4.3 I/O Diagnostics Interface.
You can find detailed information about status bits in the "Description of system CPX-E"
è 1.1 Applicable Documents.
Festo — CPX-E-PN — 2020-01a
Remedy
Remedy
Check network connection.
13