B. Ethernet/IP Objects of the CPX-FB32
B.5.2 Example: Parameterisation with the general Module Parameter

Object

0
Module no.:
Instance no.: 1
1
Parameterisation module CPX-8DE: Enable signal extension channel 5:
Object class 101 (see B.4.6)
Instance 1 (= module number)
Attribute 7 (see Tab. B/24)
2
Parameterisation module CPX-4AE-I: Lower limit channel 2
Object class 101
Instance 2 (= module number)
Attribute 82 (see Tab. B/25)
Fig. B/2: Examples for parameterisation with the general Module Parameter Object
B-40
In this example a signal extension time with a digital input
module and a lower limit value with an analogue input
module are parameterised.
1
2
2 2
3
4
8DI
AI-I
1
2
The following tables show you how to ascertain the Attributes
for the parametrizing. The parameters of the relevant
modules are entered in the tables.
Information on the parameters can be found in the
description for the relevant module.