Festo CPX-CMIX-M1-1 Manual page 29

Cpx terminal, measurement module
Hide thumbs Also See for CPX-CMIX-M1-1:
Table of Contents

Advertisement

2. Fitting and installation
Fitting
Festo P.BE-CPX-CMIX-EN en 1208a
Fit the CMIX as follows:
1. Place the CMIX in the interlinking block. Make sure that
the grooves with the power contact terminals on the
bottom of the CMIX lie above the power rails.
2. Push the CMIX carefully and without tilting as far as
possible into the interlinking block.
3. Tighten the screws at first only by hand. Place the screws
so that the self-cutting threads can be used.
4. Tighten the screws with a TORX screwdriver size T10 with
torque 0.9 ... 1.1 Nm.
The parameterisation is saved in the CMIX. Therefore, after
replacing a CMIX, check the parameters and, if necessary,
repeat the commissioning process; see chapter 3.
Observe the instructions in section A.4.
2-5

Advertisement

Table of Contents
loading

Table of Contents