Festo CPX-CMIX-M1-1 Manual page 103

Cpx terminal, measurement module
Hide thumbs Also See for CPX-CMIX-M1-1:
Table of Contents

Advertisement

B. Configuration with CPX node
Module output data
QB
Contents
QB10
Setpoint value byte 0
(LSB)
QB11
Setpoint value byte 1
QB12
Setpoint value byte 2
QB13
Setpoint value byte 3
(MSB)
QB14
Control byte CCON:
Bit
Name
0
UNIT
1
FORMAT
2
MODE
3
RESET
4
REF
5
LOAD_P
6
PARAM0
7
PARAM1
QB15
– (reserved)
Tab. B/6:
Addresses of the CMIX input and output bytes in the example Fig. B/10
(INTEL format)
Festo P.BE-CPX-CMIX-EN en 1208a
Module input data
Address
IB
Q10.0 ... 7
IB10
Q11.0 ... 7
IB11
Q12.0 ... 7
IB12
Q13.0 ... 7
IB13
IB14
Q14.0
Q14.1
Q14.2
Q14.3
Q14.4
Q14.5
Q14.6
Q14.7
Q15.0 ... 7
IB15
The following examples show a variable table each for various
format and data formats; see also section 3.3.
Contents
Actual value byte 0
(LSB)
Actual value byte 1
Actual value byte 2
Actual value byte 3
(MSB)
Status byte SCON:
Bit
Name
0
ERROR0
1
ERROR1
2
ERROR2
3
ERROR3
4
REF_OK
5
ACK
6
7
ERROR
– (reserved)
Address
I10.0 ... 7
I11.0 ... 7
I12.0 ... 7
I13.0 ... 7
I14.0
I14.1
I14.2
I14.3
I14.4
I14.5
I14.6
I14.7
I15.0 ... 7
B-17

Advertisement

Table of Contents
loading

Table of Contents