Purpose
Operation mode selection
Started in network operation mode
Selection of control source
6.17.1
Operation mode selection (Pr. 79)
Used to select the operation mode of the inverter.
Mode can be changed as desired between operation using external command signals (external
operation), operation from the operation panel and PU (FR-PU07/FR-PU04) (PU operation),
combined operation of PU operation and external operation (external/PU combined operation),
and network operation (when RS485 communication is used).
Pr.
Name
No.
Operation mode
79
selection
The above parameter can be changed during a stop in any operation mode.
The priorities of the frequency commands when Pr. 79 = "3" are "Multi-speed operation (RL/
RM/RH/REX) > PID control (X14) > terminal 4 analog input (AU) > digital input from the
operation panel".
6 - 172
Parameters that must be set
Operation mode selection
Operation mode at power on
Selection of control source, speed com-
mand source and control location during
communication operation
Initial
Setting
Description
Value
Range
External/PU switchover mode
0
External operation mode at power on
1
Fixed to PU operation mode
Fixed to external operation mode
Operation can be performed by switching
2
between external and NET operation
mode
Combined operation mode 1
Running frequency:
Operation panel, and PU (FR-PU04/
FR-PU07) setting or external signal input
3
[multi-speed setting, across terminals
4-5 (valid when AU signal turns on)]
Start signal:
External signal input (terminal STF, STR)
External/PU combined operation mode 2
Running frequency:
External signal input (terminal 2, 4, JOG,
0
multi-speed setting, etc.)
4
Start signal:
Enter from the RUN key of the operation
panel and the FWD/REV keys of the PU
(FR-PU04/FR-PU07)
Switchover mode
Switchover between PU operation, exter-
6
nal operation, and NET operation is avail-
able while keeping the same operation
status.
External operation mode (PU operation
interlock)
X12 signal ON:
Operation mode can be shifted to PU
7
operation mode (output stop during
external operation)
X12 signal OFF:
Operation mode can not be switched to
PU operation mode.
Parameter
Refer to
Section
Pr. 79
6.17.1
Pr. 79, Pr. 340
6.17.2
Pr. 338, Pr. 339,
6.17.3
Pr. 551
Parameters referred to
15
Jog frequency
4–6
Multi-speed
24–27
operation
232–239
75
Reset selection/
disconnected PU
detection/
PU stop selection
161
Frequency setting/
key lock operation
selection
178–182
Input terminal func-
tion selection
190/192/
Output terminal
197
function selection
340
Communication
start-up mode
selection
Refer to
Section
6.5.2
6.5.1
6.16.1
6.21.3
6.9.1
6.9.5
6.17.2