Mitsubishi Electric FR-D720S SC EC Instruction Manual page 332

Fr-d700 series
Table of Contents

Advertisement

Selection of operation mode and operation location
Switching of operation mode by external terminal (X65, X66)
When Pr. 79 = any of "0, 2, 6", the operation mode switching signals (X65, X66) can be used to
change the PU or external operation mode to network operation mode during a stop (during a
motor stop or start command off). (Pr. 79 = 6 switch-over mode can be changed during oper-
ation)
When switching from network operation mode to PU operation mode:
Set Pr. 79 to "0" (initial value) or "6".
Set "10" in Pr. 340.
Set "65" to any of Pr. 178 to Pr. 182 to assign the PU-NET operation switching signal (X65)
to the external terminal.
The operation mode changes to PU operation mode when the X65 signal turns on, or to
network operation mode when the X65 signal turns off.
Pr. 340
10
Tab. 6-40: Operation mode switching by signal X65
NET operation mode when the X66 signal is on.
PU operation mode is selected when the X16 signal is off.
External operation mode when the X16 signal is on.
6 - 182
Pr. 79
ON (PU)
0
(initial setting)
operation mode
1
2
3 / 4
External/PU combined operation mode External/PU combined mode fixed
6
operation mode
X12 (MRS)
Switching among the External and PU
ON
operation mode is enabled
7
X12 (MRS)
OFF
X65 Signal State
OFF (NET)
PU
NET operation
mode
PU operation mode
NET operation mode
PU
NET operation
mode
External operation mode
Remarks
Fixed to PU operation mode
Fixed to NET operation mode
Operation mode can be switched with
operation continued
Output stop in external operation mode
Forcibly switched to external operation
mode
Parameter