Meters And Measuring Methods - Mitsubishi Electric FR-D720S SC EC Instruction Manual

Fr-d700 series
Table of Contents

Advertisement

Troubleshooting
7.7

Meters and measuring methods

NOTE
For further information about measurements at the inverter refer to section 8.2.
Since voltages and currents in the primary and secondary side of the inverter include harmonics,
different meters indicate different measured values.
When the inverter-to-motor wiring length is large, especially in the 400V class, large-capacity
models, the meters and CTs may generate heat due to line-to-line leakage current. Therefore,
choose the equipment which has enough allowance for the current rating.
When measuring and indicating the output voltage and output current of the inverter, it is rec-
ommended to utilize the AM-5 terminal output function of the inverter. To do this, assign the re-
quired parameter to the terminal.
When using measuring instruments for the normal frequency range, carry out the measure-
ments as described below.
Single-phase, 230 V
Three-phase, 400 V
Power supply
Instrument types
* At, As, Vt, Vs, W12, W13 are only for the three-phase power input specification models.
Fig. 7-7: Measurements at the main circuit
FR-D700 SC EC
Input voltage
Input current
Inverter
P/+ N/–
Meters and measuring methods
Output voltage
Output current
To the motor
Moving-iron type
Electro dynamometer type
Moving-coil type
Rectifier type
I002040E
7 - 31