Frequency Setting By External Terminals - Mitsubishi Electric FR-D720S SC EC Instruction Manual

Fr-d700 series
Table of Contents

Advertisement

Frequency setting by external terminals

6.5
Frequency setting by external terminals
Purpose
Make frequency setting by combina-
tion of terminals
Perform jog operation
Infinitely variable speed setting by
terminals
6.5.1
Multi-speed setting operation
(Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to Pr. 239)
The frequency inverters have 15 fixed setting frequencies (speeds) which can be preset by the
user as required via parameters 4, 5, 6, 24 to 27 as well as via parameters 232 to 239.
Any speed can be selected by merely turning on-off the contact signals (RH, RM, RL, REX
signals).
Pr.
Name
No.
Multi-speed setting
4
(high speed)
Multi-speed setting
5
(middle speed)
Multi-speed setting
6
(low speed)
Multi-speed setting
24
(speed 4)
Multi-speed setting
25
(speed 5)
Multi-speed setting
26
(speed 6)
Multi-speed setting
27
(speed 7)
Multi-speed setting
232
(speed 8)
Multi-speed setting
233
(speed 9)
Multi-speed setting
234
(speed 10)
Multi-speed setting
235
(speed 11)
Multi-speed setting
236
(speed 12)
Multi-speed setting
237
(speed 13)
Multi-speed setting
238
(speed 14)
Multi-speed setting
239
(speed 15)
The above parameters allow its setting to be changed during operation in any operation mode
even if "0" (initial value) is set in Pr. 77 "Parameter write selection".
The above parameters can be set when Pr. 160 = 0.
6 - 48
Parameters that must be set
Multi-speed operation
Jog operatio
Remote setting function
Initial
Setting Range Description
Value
Set the frequency when RH
50Hz
0–400Hz
turns on.
Set the frequency when RM
30Hz
0–400Hz
turns on.
Set the frequency when RL turns
10Hz
0–400Hz
on.
9999
0–400Hz/9999
9999
0–400Hz/9999
9999
0–400Hz/9999
9999
0–400Hz/9999
9999
0–400Hz/9999
Frequency from speed 4 to
9999
0–400Hz/9999
speed 15 can be set according
to the combination of the RH,
RM, RL and REX signals.
9999
0–400Hz/9999
9999: not selected
9999
0–400Hz/9999
9999
0–400Hz/9999
9999
0–400Hz/9999
9999
0–400Hz/9999
9999
0–400Hz/9999
Parameter
Refer to
Section
Pr. 4–Pr. 6,
6.5.1
Pr. 24–Pr. 27
Pr. 232–Pr. 239
Pr. 15, Pr. 16
6.5.2
Pr. 59
6.5.3
Parameters referred to
15
JOG frequency
59
Remote function
selection
79
Operation mode
selection
178–182
Input terminal
function selection
Refer to
Section
6.5.2
6.5.3
6.17.1
6.9.1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-d740 sc ec

Table of Contents