Detection of output frequency (SU, FU, Pr. 41 to Pr. 43)

The inverter output frequency is detected and output to the output signal.
Pr.
Name
No.
Up-to-frequency
41
sensitivity
Output frequency
42
detection
Output frequency
43
detection for reverse
rotation
The above parameters can be set when Pr. 160 = 0.
Up-to-frequency sensitivity (SU, Pr. 41)
When the output frequency reaches the set frequency, the up-to-frequency signal (SU) is out-
put. The Pr. 41 value can be adjusted within the range 0% to ±100% on the assumption that the
set frequency is 100%.
This parameter can be used to ensure that the running frequency has been reached to provide
the operation start signal etc. for related equipment.
When using the SU signal, set "1 (positive logic) or 101 (negative logic)" in Pr. 190, Pr. 192 or
Pr. 197 to assign function to the output terminal.
Set
frequency
SU
signal
FR-D700 SC EC
Initial
Setting
Description
Value
Range
10%
0–100%
Set the level where the SU signal turns on.
Set the frequency where the FU signal
6Hz
0–400Hz
turns on.
Set the frequency where the FU signal
0–400Hz
turns on in reverse rotation.
9999
9999
Same as Pr. 42 setting
Running frequency
Hz
Function assignment of external terminals
Fig. 6-53:
Output of the SU signal
Adjustment
range
Pr. 41
t
Parameters referred to
190/192/
Output terminal
197
function selection
Refer to
Section
6.9.5
I000020C
6 - 103