Start Signal Selection (Terminal Stf, Str, Stop, Pr. 250) - Mitsubishi Electric FR-D720S SC EC Instruction Manual

Fr-d700 series
Table of Contents

Advertisement

Function assignment of external terminals
6.9.4

Start signal selection (Terminal STF, STR, STOP, Pr. 250)

You can select the operation of the start signal (STF/STR).
Used to select the stopping method (deceleration to a stop or coasting) when the start signal
turns off. Used to stop the motor with a mechanical brake, etc. together with switching off of the
start signal. (Refer to section 6.8.3 for stop selection.)
Pr.
Initial
Name
No.
Value
250
Stop selection
9999
The above parameter can be set when Pr. 160 = 0.
2-wire type (terminals STF and STR)
A two-wire type connection is shown below.
In the initial setting, the forward/reverse rotation signals (STF/STR) are used as start and stop
signals. Turn on either of the forward and reverse rotation signals to start the motor in the cor-
responding direction. If both are turned off (or on) during operation, the inverter decelerates to
a stop.
The speed setting signal may either be given by entering 0 to 10V DC across the speed setting
input terminal 2-5, by setting the required values in Pr. 4 to Pr. 6 "Multi-speed setting" (high, mid-
dle, low speeds), etc. (For multi-speed operation, refer to section 6.5.1).
When Pr. 250 is set to any of "1000 to 1100, 8888", the STF signal becomes a start command
and the STR signal a forward/reverse command.
Forward rotation start
Reverse rotation start
6 - 94
Description
Setting
Start Signal
Range
(STF/STR)
STF: Forward
rotation start
0–100s
STR: Reverse rotation
start
STF: Start signal
1000s
STR: Forward/reverse
1100s
signal
STF: Forward
rotation start
9999
STR: Reverse
rotation start
STF: Start signal
8888
STR: Forward/reverse
signal
Inverter
ON
ON
Parameters referred to
Stop Operation
The motor is coasted to
a stop when the preset
time elapses after the
178–182
start signal is turned off.
The motor is coasted to
a stop (Pr. 250 − 1000)s
after the start signal is
turned off.
When the start signal is
turned off, the motor
decelerates to stop.
Fig. 6-47:
2-wire type connection (Pr. 250 = 9999)
Time
Parameter
Refer to
Section
4–6
Multi-speed
6.5.1
setting
Input terminal
6.9.1
function selection
I001148E

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-d740 sc ec

Table of Contents