Pr. 125, Pr. 126, Pr. 241, C2 (Pr. 902) To C7 (Pr. 905)] - Mitsubishi Electric FR-D720S SC EC Instruction Manual

Fr-d700 series
Table of Contents

Advertisement

Parameter
6.15.3
Bias and gain of frequency setting voltage (current)

[Pr. 125, Pr. 126, Pr. 241, C2 (Pr. 902) to C7 (Pr. 905)]

You can set the magnitude (slope) of the output frequency as desired in relation to the frequency
setting signal (0 to 5V DC, 0 to 10V DC or 0/4 to 20mA DC).
These parameters can be used to configure the inverter precisely for set point signals that either
exceed or do not quite reach 5V or 10V or 20mA. These settings can also be used to configure
inverse control (i.e. high output frequency at minimum set point signal, minimum output
frequency at maximum set point signal).
Pr. No. Name
Terminal 2 frequency setting
125
gain frequency
Terminal 4 frequency setting
126
gain frequency
Analog input display unit
241
switchover
C2
Terminal 2 frequency setting
(902)
bias frequency
C3
Terminal 2 frequency setting
(902)
bias
C4
Terminal 2 frequency setting
(903)
gain
C5
Terminal 4 frequency setting
(904)
bias frequency
C6
Terminal 4 frequency setting
(904)
bias
C7
Terminal 4 frequency setting
(905)
gain
The above parameters can be set when Pr. 160 = 0.
The parameter number in parentheses is the one for use with the operation panel (PA02)
for the FR-E500 series or parameter unit (FR-PU04/FR-PU07).
The above parameter allow its setting to be changed during operation in any operation mode
even if "0" (initial value) is set in Pr. 77 "Parameter write selection".
FR-D700 SC EC
Initial
Setting
Description
Value
Range
Set the frequency of terminal 2
50Hz
0–400Hz
input gain (maximum).
Set the frequency of terminal 4
50Hz
0–400Hz
input gain (maximum).
0
Displayed in %
0
Displayed in
1
V/mA
Set the frequency on the bias side
0Hz
0–400Hz
of terminal 2 input.
Set the converted % of the bias
0%
0–300%
side voltage (current) of terminal
2 input.
Set the converted % of the gain
100%
0–300%
side voltage of terminal 2 input.)
Set the frequency on the bias side
0Hz
0–400Hz
of terminal 4 input.
Set the converted % of the bias
20%
0–300%
side current (voltage) of terminal
4 input.
Set the converted % of the gain
100%
0–300%
side current (voltage) of terminal
4 input.
Frequency setting by analog input (terminal 2, 4)
Parameters referred to
20
73
Select the unit of
267
analog input
display.
79
Refer to
Section
Acceleration/
6.6.1
deceleration
reference
frequency
Analog input
6.15.1
selection
Terminal 4 input
6.15.1
selection
Operation mode
6.17.1
selection
6 - 153

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-d740 sc ec

Table of Contents