Parameter
Parameter
Func-
Name
tion
Frequency monitoring
55
reference
Current monitoring
56
reference
57
Restart coasting time
58
Restart cushion time
Automatic restart after
instantaneous power
162
failure selection
Stall prevention opera-
165
tion level for restart
Frequency search gain
298
Rotation direction
detection selection at
299
restarting
Acceleration time at a
611
restart
Tab. 6-1:
Parameter overview (7)
FR-D700 SC EC
Incre-
Initial
Setting
ments
value
range
0.01Hz
50Hz
0–400Hz
Rated
inverter
0.01
0–500
output
current
0
0.1s
9999
0.1–5s
9999
0,1 s
1 s
0–60 s
0
1
1
1
10
11
0.1%
150%
0–200%
0–32767
1
9999
9999
0
1
1
0
9999
0–3600s
0.1s
9999
9999
Description
Set the full-scale value to output
the output frequency monitor
value to terminal AM.
Set the full-scale value to output
the output current monitor value
to terminal AM.
The coasting time is as follows:
FR-D720S-070SC or less,
FR-D740-036SC or less:. . . . 1 s,
FR-D720S-100SC,
FR-D740-050SC or more:. . . 2 s
Set the waiting time for inverter-
triggered restart after an instanta-
neous power failure.
No restart
Set a voltage starting time at
restart.
With fre-
quency search
Without fre-
quency search
(Reduced
When using the
voltage sys-
frequency search,
tem)
consider the wir-
ing length limit.
Frequency
(Refer to page
search at
3-11.)
every start
Reduced
voltage sys-
tem at every
start
Consider the rated inverter current
as 100% and set the stall preven-
tion operation level during restart
operation.
When offline auto tuning is per-
formed under V/f control, fre-
quency search gain necessary for
frequency search for automatic
restart after instantaneous power
failure is set as well as the motor
constants (R1).
Uses the Mitsubishi motor (SF-JR,
SF-HRCA) constants
Without rotation direction detection
With rotation direction detection
When Pr. 78 = "0", the rotation
direction is detected.
When Pr. 78 = "1", "2", the rotation
direction is not detected.
Set the acceleration time to reach
the set frequency at a restart.
Acceleration time for restart is the
normal acceleration time (e.g.
Pr. 7).
Parameter overview
All
Para-
Para-
Para-
meter
meter
meter
copy
clear
clear
Refer
to
page
✔: enabled
—: disabled
6-118
6-123
6 - 7