Parameter
Inverter operation ready signal (RY) and inverter running signal (RUN)
When the inverter is ready to operate, the output of the operation ready signal (RY) is on. It is
also on during inverter running.
When the output frequency of the inverter rises to or above Pr. 13 "Starting frequency", the out-
put of the inverter running signal (RUN) is turned on. During an inverter stop or DC injection
brake operation, the output is off.
When using the RY or RUN signal, set "11 (source logic)" or "111 (sink logic)" (RY) or "0 (source
logic)" or "100 (sink logic)" (RUN) to any of Pr. 190, Pr. 192 or Pr. 197 to assign the function to
the output terminal.
Fig. 6-51: Ready and motor running signals
Output
Signal
RY
RUN
Tab. 6-16: Output signal output
This signal turns OFF during power failure or undervoltage.
Output is shutoff under conditions such as a fault occurrence, MRS signal ON, and the safety
stop operation.
NOTE
The RUN signal (positive logic) is assigned to the terminal RUN in the initial setting.
FR-D700 SC EC
Power supply
ON
Starting frequency Pr. 13
Reset processing
Start
Start
Signal
Signal ON
OFF
(during
(during
stop)
stop)
ON
ON
OFF
OFF
Function assignment of external terminals
ON
OFF
ON
ON
ON
Start
Under DC
Signal ON
Output
Injection
(during
shutoff
Brake
operation)
ON
ON
ON
OFF
OFF
DC injection brake operation point
DC injection brake operation
Time
OFF
OFF
Automatic Restart after
Instantaneous Power Failure
Coasting
Start
Start
Signal
Signal ON
OFF
OFF
ON
OFF
OFF
I001796E
Restart-
ing
ON
ON
6 - 101