Basic settings
5.2.5
Perform frequency setting by analog current input
An external current source is connection to the frequency inverter for setpoint default setting.
Fig. 5-18: Frequency setting by analog current input
● Pr. 79 "Operation mode selection" must be set to "4" (external/PU combined operation
mode 2).
● Turn the AU signal on.
● Use the RUN key to give a start command.
NOTE
For the analog current input (0/4 to 20 mA) to become effective for setpoint default setting,
the AU signal on the AU terminal must be activated. This is done, for example, by means of
a bridge as shown in Fig. 5-18.
FR-D700 SC EC
Power supply
AU signal
Current signal
source
(0/4–20mA DC)
PU operation mode
Inverter
Motor
Operation
panel
I0020206E
5 - 29