Selection Of Operation Mode And Operation Location; Operation Mode Selection (Pr. 79) - Mitsubishi Electric FR-F740-00023-EC Instruction Manual

Frequency inverter
Hide thumbs Also See for FR-F740-00023-EC:
Table of Contents

Advertisement

Selection of operation mode and
operation location

3.17 Selection of operation mode and operation location

Purpose
Operation mode selection
Started in network operation mode
Selection of control location

3.17.1 Operation mode selection (Pr. 79)

Used to select the operation mode of the inverter.
Pr.78
Mode can be changed as desired between operation using external signals (external operation), operation from
page 146
the PU (FR-DU07/FR-PU04), combined operation of PU operation and external operation (external/PU combined
Pr.80
page 58
operation, and network operation (when RS-485 terminals or a communication option is used).
Parameter
Name
Number
Operation
79
mode
selection
The above parameters can be changed during a stop in any operation mode.
148
Operation mode selection
Operation mode at power on
Sslection of control source, speed
command source and control location
during communication operation
Initial
Setting
Value
Range
Use external/PU switchover mode (press
0
between the PU and external operation mode.
At power on, the inverter is in the external operation
mode.
1
Fixed to PU operation mode
Fixed to external operation mode
2
Operation can be performed by switching between the
external and Net operation mode.
External/PU combined operation mode 1
Running frequency
PU (FR-DU07/FR-PU04)
3
setting or external signal input
(multi-speed setting, across
terminals 4-5 (valid when AU
signal turns on)).
External/PU combined operation mode 2
0
Running frequency
4
External signal input
(Terminal 2, 4, 1, JOG, multi-
speed selection, etc.)
Switch-over mode
6
Switch among PU operation, external operation, and NET
operation while keeping the same operation status.
External operation mode (PU operation interlock)
X12 signal ON*
Operation mode can be switched to the PU operation
mode.
7
(output stop during external operation)
X12 signal OFF*
Operation mode can not be switched to the PU
operation mode.
Parameter that must be set
Description
Start signal
External signal input
(terminal STF, STR)
Start signal
Input from the PU (FR-
DU07/FR-PU04)
(
,
Refer to page
Pr. 79
148
Pr. 79, Pr. 340
156
Pr. 338, Pr. 339,
157
Pr. 550, Pr. 551
LED Indication
: Off
: On
External operation mode
to switch
PU operation mode
External operation mode
NET operation mode
)
PU operation mode
External operation mode
NET operation mode
PU operation mode
External operation mode