Mitsubishi Electric FR-D720S SC EC Instruction Manual page 250

Fr-d700 series
Table of Contents

Advertisement

Function assignment of external terminals
Setting
Terminal Function
Source
Sink
Logic
Logic
90
190
Y90
91
191
Y91
93
193
Y93
95
195
Y95
96
196
REM
98
198
99
199
ALM
9999
Tab. 6-15:
Output terminal function assignment (3)
Note that when the frequency setting is varied using an analog signal or the digital dial of
the operation panel, the output of the SU (up to frequency) signal may alternate on and off
depending on that varying speed and the timing of the varying speed due to acceleration/
deceleration time setting. (The output will not alternate on and off when the acceleration/
deceleration time setting is "0s".)
NOTES
The same function may be set to more than one terminal.
When the function is executed, the terminal conducts at the setting of any of "0" to "99", and
does not conduct at the setting of any of "100" to "199".
Changing the terminal assignment using Pr. 190, Pr. 192 or Pr. 197 may affect the other
functions. Make setting after confirming the function of each terminal.
Do not assign signals which repeat frequent ON/OFF to A, B, and C. Otherwise, the life of
the relay contact decreases.
Refer to section 3.4 for the common terminal of each terminal.
6 - 100
Life alarm
Alarm output 3 (power-off signal)
Current average value monitor
signal
Maintenance timer signal
Remote Output
LF
Minor fault output
Alarm output
No function
Operation
Output when any of the con-
trol circuit capacitor, main cir-
cuit capacitor and inrush
current limit circuit or the
cooling fan approaches the
end of its service life.
Output when an error occurs
due to the circuit failure or
connection alarm of the
inverter.
Average current value and
maintenance timer value are
output as pulses. The signal
can not be set in Pr. 192
"ABC terminal function selec-
tion".
Output when Pr. 503 rises to
or above the Pr. 504 setting.
Output to the terminal when a
value is set to the parameter.
Output when a minor fault
(fan failure or communication
error warning) occurs.
Output when the inverter's
protective function is acti-
vated to stop the output
(major fault). The signal out-
put is stopped when a reset
turns on.
Parameter
Related Parame-
Refer to
ters
Page
Pr. 255–Pr. 259
6-272
6-102
Pr. 555–Pr. 557
6-277
Pr. 503, Pr. 504
6-276
Pr. 495, Pr. 496
6-107
6-198,
Pr. 121, Pr. 244
6-270
6-102