E-Clipse macro

This macro configures for an E-Clipse Bypass device which can bypass the drive
and connect the motor direct on-line. When using direct speed reference in AUTO
mode or process PID, see
+
+
mA
9902
1001
1002
1201
1601
General considerations
X1
Signal cable shield (screen)
1
SCR
External reference 0(2)...10 V or 0(4)...20 mA
2
AI1
Analog input circuit common
3
AGND
Reference voltage 10 VDC
4
10V
PID feedback: 0(2)...10 V or 0(4)...20 mA
5
AI2
Analog input circuit common
6
AGND
Output frequency: 0(4)...20 mA
7
AO1
mA
Output current: 0(4)...20 mA
8
AO2
Analog output circuit common
9
AGND
Auxiliary voltage output +24 VDC
10 24V
Auxiliary voltage output common
11 GND
Digital input common for all
12 DCOM
Not configured
13 DI1
Not configured
14 DI2
Not configured
15 DI3
Not configured
16 DI4
Not configured
17 DI5
Not configured
18 DI6
Relay output 1 (P 1401)
19 RO1C
Default operation: Ready =>19 connected to 21
20 RO1A
21 RO1B
Relay output 2 (P 1402)
22 RO2C
Default operation: Running =>22 connected to 24
23 RO2A
24 RO2B
25 RO3C
Relay output 3 (P 1403)
Default operation: Fault (-1) =>25 connected to 27
26 RO3A
27 RO3B
Parameters Changed Relative to HVAC Default
Parameter
15 (
APPLIC MACRO
1
10 (
EXT
COMMANDS
2
10 (
EXT
COMMANDS
0 (
CONST SPEED SEL
7 (
RUN ENABLE
(Fault => 25 connected to 26)
Value
-
)
1608
E
CLIPSE
)
5303
COMM
)
5304
COMM
)
5305
NOT SEL
)
COMM
on page 1-49.
J1 Jumper Settings
J1
...
AI1: 0(4)
20 mA
...
AI2: 0(4)
20 mA
Parameter
1
7 (
START ENABLE
76.8
EFB BAUD RATE
2 (8
EFB PARITY
1 (
EFB CTRL PROFILE
Application macros
1-65
J1
Value
)
COMM
/
KB
S
1)
EVEN
)
DCU PROFILE