ABB ACH550-UH User Manual page 178

Ach550 series, hvac drives (1...550 hp), e-clipse bypass drives (1...400 hp), packaged drives with disconnect (1...550 hp)
Hide thumbs Also See for ACH550-UH:
Table of Contents

Advertisement

1-174
Code Description
8117 NR OF AUX MOT
Sets the number of auxiliary motors.
• Each auxiliary motor requires a relay output, which the drive uses to send start/stop signals.
• The Autochange function, if used, requires an additional relay output for the speed regulated motor.
• The following describes the set-up of the required relay outputs.
Relay outputs
As noted above, each auxiliary motor requires a relay output, which the drive uses to send start/stop signals. The
following describes how the drive keeps track of motors and relays.
• The ACH550 provides relay outputs RO1...RO3.
• An external digital output module (OREL-01) can be added to provide relay outputs RO4...RO6.
• Parameters 1401...1403 and 1410...1412 define, respectively, how relays RO1...RO6 are used – the parameter
value 31
defines the relay as used for PFA.
PFA
• The ACH550 assigns auxiliary motors to relays in ascending order. If the Autochange function is disabled, the first
auxiliary motor is the one connected to the first relay with a parameter setting = 31
Autochange function is used, the assignments rotate. Initially, the speed regulated motor is the one connected to
the first relay with a parameter setting = 31
with a parameter setting = 31
ACH550
Standard PFA mode
• The fourth auxiliary motor uses the same reference step, low frequency and start frequency values as the third
auxiliary motor.
Parameters
Group 81: PFA Control
Range
0...4
, the first auxiliary motor is the one connected to the second relay
PFA
, and so on.
PFA
ACH550
ACH550-UH User's Manual
Resolution
Default
1
1
, and so on. If the
PFA
Relay logic
PFA with Autochange mode
S