Group 37: USER LOAD CURVE
This group defines supervision of user adjustable load curves (motor torque as a
function of frequency). The curve is defined by five points.
Code Description
3701 USER LOAD C MODE
Supervision mode for the user adjustable load
curves.
This functionality replaces the former underload
supervision in
Group 30: FAULT
emulate it, see section
obsolete underload supervision
0 =
– Supervision is not active.
NOT SEL
1 =
– Supervision for the torque
UNDERLOAD
dropping below the underload curve.
2 =
– Supervision for the torque
OVERLOAD
exceeding the overload curve.
3 =
– Supervision for the torque dropping
BOTH
below the underload curve or exceeding the
overload curve.
3702 USER LOAD C FUNC
Action wanted during load supervision.
1 =
– A fault is generated when the condition defined by 3701
FAULT
the time set by 3703
2 =
– An alarm is generated when the condition defined by 3701
ALARM
than half of the time defined by 3703
3703 USER LOAD C TIME
Defines the time limit for generating a fault.
• Half of this time is used as the limit for generating an alarm.
3704 LOAD FREQ 1
Defines the frequency value of the first load curve definition point.
• Must be smaller than 3707
3705 LOAD TORQ LOW 1
Defines the torque value of the first underload curve definition point.
• Must be smaller than 3706
3706 LOAD TORQ HIGH 1
Defines the torque value of the first overload curve definition point.
3707 LOAD FREQ 2
Defines the frequency value of the second load curve definition point.
• Must be smaller than 3710
3708 LOAD TORQ LOW 2
Defines the torque value of the second underload curve definition point.
• Must be smaller than 3709
3709 LOAD TORQ HIGH 2
Defines the torque value of the second overload curve definition point.
3710 LOAD FREQ 3
Defines the frequency value of the third load curve definition point.
• Must be smaller than 3713
Group 37: User Load Curve
Range
0...3
FUNCTIONS. To
Correspondence with the
on page 1-148.
1, 2
.
USER LOAD C TIME
USER LOAD C TIME
10...400 s
0...500 Hz
2.
LOAD FREQ
0...600%
1.
LOAD TORQ HIGH
0...600%
0...500 Hz
3.
LOAD FREQ
0...600%
2.
LOAD TORQ HIGH
0...600%
0...500 Hz
4.
LOAD FREQ
Resolution
1
Motor torque (%)
P3706
P3709
Allowed operating area
P3705
P3708
P3704
P3707
1
USER LOAD C MODE
USER LOAD C MODE
.
1 s
1 Hz
1%
1%
1 Hz
1%
1%
1 Hz
1-147
Default
0 (
)
NOT SEL
Overload area
P3712
P3715
P3718
P3714
P3717
P3711
Underload area
P3710
P3713
P3716
Output frequency (Hz)
1 (
)
FAULT
has been valid longer than
has been valid longer
20 s
5 Hz
10%
300%
25 Hz
15%
300%
43 Hz
Parameters