2-48
Communications Control (16) [COMM CTRL]
If configured for Communications Control, the relay is energized when the
appropriate ON command is provided over the serial communications connection.
The relay is de-energized when the appropriate OFF command is provided over the
serial communications connection.
System Alarm (17) [SYS ALARM]
If configured for System Alarm, the relay is energized when a drive/bypass alarm is
present. The specific nature of the alarm is indicated on either the drive control panel
display or the bypass control panel display, depending upon the origination of the
alarm. The System Alarm relay is de-energized during normal operation.
Bypass Fault/Alarm (18) [BYP FLT/ALM]
If configured for Bypass Fault/Alarm, the relay is energized when either a bypass
fault has occurred, the bypass motor overload/underload protection has tripped or
when a bypass alarm condition is present. The Bypass Fault/Alarm relay is de-
energized during normal operation.
Bypass Overload (19) [BYP OVERLD]
If configured for Bypass Overload, the relay is energized when the bypass motor
overload level has exceeded the programmed protection setting. The Bypass
Overload relay is de-energized during normal operation.
Bypass Underload (20) [BYP UNDERLD]
If configured for Bypass Underload, the relay is energized when the bypass motor
underload level has fallen below the programmed protection setting. This output is
often used for broken belt indication. The Bypass Underload relay is de-energized
during normal operation.
PCB Overtemperature (21) [PCB OVERTMP]
If configured for PCB Overtemperature, the relay is energized when the temperature
of the bypass control, printed circuit board has exceeded the fixed protection setting.
The PCB Overtemperature relay is de-energized during normal operation.
System Underload (22) [SYS UNDERLD]
If configured for System Underload, the relay is energized when either the drive or
bypass motor underload level has fallen below the programmed protection setting.
This output is often used for broken belt indication. The System Underload relay is
de-energized during normal operation.
System Fault (23) [SYSTEM FLT]
If configured for System Fault, the relay is energized when either a drive/bypass fault
has occurred or the bypass motor overload/underload protection has tripped. The
System Fault relay is de-energized during normal operation.
System Fault/Alarm (24) [SYS FLT/ALM]
If configured for System Fault/Alarm, the relay is energized when either a drive/
bypass fault has occurred, the bypass motor overload/underload protection has
tripped or when a drive/bypass alarm condition is present. The System Fault/Alarm
relay is de-energized during normal operation.
Bypass functions overview
ACH550 E-Clipse Bypass User's Manual