ABB ACH550-UH User Manual page 164

Ach550 series, hvac drives (1...550 hp), e-clipse bypass drives (1...400 hp), packaged drives with disconnect (1...550 hp)
Hide thumbs Also See for ACH550-UH:
Table of Contents

Advertisement

1-160
Group 42: EXT / TRIM PID
This group defines the parameters used for the second PID controller (PID2), which
is used for the External / Trimming PID.
The operation of parameters 4201
(PID1) parameters 4001...4021.
Code Description
4201
See 4001 ...4021
...
Note: The Default value for parameter 4201 is 1.0.
4221
The Default value for parameter 4202 is 60.0 s.
The Default value for parameter 4210 is 1 (
4228 ACTIVATE
Defines the source for enabling the external PID function.
• Requires 4230
0 =
– Disables external PID control.
NOT SEL
1 =
1 – Defines digital input
DI
• Activating the digital input enables external PID control.
• De-activating the digital input disables external PID control.
2...6 =
2...
6 – Defines digital input
DI
DI
• See
1 above.
DI
7 =
– Defines the start command as the control for enabling external PID control.
DRIVE RUN
• Activating the start command (drive is running) enables external PID control.
8 =
– Defines the power-on as the control for enabling external PID control.
ON
• Activating power to the drive enables external PID control.
9...12 =
TIMED FUNC
function active enables external PID control).
• See
Group 36: TIMED
-1 =
1(
) – Defines an inverted digital input
DI
INV
• Activating the digital input disables external PID control.
• De-activating the digital input enables external PID control.
-2...-6 =
2(
)...
DI
INV
control.
• See
1(
) above.
DI
INV
4229 OFFSET
Defines the offset for the PID output.
• When PID is activated, output starts from this value.
• When PID is deactivated, output resets to this value.
• Parameter is active when 4230
4230 TRIM MODE
Selects the type of trim, if any. Using the trim it is possible to combine a corrective factor to the drive reference.
0 =
– Disables the trim function.
NOT SEL
1 =
PROPORTIONAL
2 =
– Adds a trim factor based on the control loop's maximum limit.
DIRECT
4231 TRIM SCALE
Defines the multiplier (as a percent, plus or minus) used in the trim mode.
Parameters
Group 42: Ext / Trim PID
Range
-6...12
= 0 (
).
TRIM MODE
NOT SEL
1 as the control for enabling external PID control.
DI
2...
DI
DI
1...4 – Defines the Timed function as the control for enabling external PID control (Timed
FUNCTIONS.
6(
) – Defines an inverted digital input
DI
INV
0.0...100.0%
= 0 (trim mode is not active).
TRIM MODE
0...2
– Adds a trim factor that is proportional to the rpm/Hz reference.
-100.0%...100.0%
4221 is analogous with Process PID set 1
...
Resolution
1).
AI
-
6 as the control for enabling external PID control.
1 as the control for enabling external PID control.
DI
2...
6 as the control for enabling external PID
DI
DI
0.1%
1
0.1%
ACH550-UH User's Manual
Default
0 (
)
NOT SEL
0.0%
0 (
)
NOT SEL
0.0%
S