Embedded fieldbus
FLN Detailed Point Descriptions
Point
CTRL ADDRESS The FLN address of the bypass. It can be set by FLN and by
the panel.
APPLICATION
This is the Application ID for FLN on the E-Clipse Bypass.
This ID is assigned by Siemens for each unique application.
It correlates directly to a particular point list approved at the
time of release. Therefore, this point list shall remain fixed
once approval is granted. Any changes to the point list shall
require a new Application ID and re-approval by Siemens.
The Application ID assigned to the E-Clipse bypass is 2737.
INPUT VOLT
Average of line-line input voltage
CURRENT
Measured output current.
SYS
This point indicates if the system is in an underload
UNDRLOAD
condition. Detection of this condition is done with bypass
parameters 3001-3003.
PCB TEMP
DEG C of bypass board
KW HOURS
Bypass-mode kilowatt hours
RUN TIME
Bypass mode run hours
A-B VOLT
Phase A - Phase B voltage
B-C VOLT
Phase B - Phase C voltage
C-A VOLT
Phase C - Phase A voltage
OVRD TIME
This is 1 of 5 mandatory FLN points required for
compatibility with Siemens control systems. It has no
functionality in the bypass application.
MTR RUNNING
This point indicates the system's run status, regardless of
control source (1 = RUN, 0 = STOP).
RUN.STOP CMD This point is commanded by FLN to start the system.
Bypass parameter 1601 must be set to COMM for FLN to
control the run state of the system.
OVERRIDE ACT
This point indicates if the bypass is in override 1 or override
2.
OVERRID CMD
This point is commanded by FLN to select override 2.
Override 2 is configured by parameters in bypass group 17.
SYSTEM
This point indicates the system is ready to accept a run
READY
command (1 = READY, 0 = NOTRDY).
SYS STARTED
This point the system has received a run command and is
started. It may or may not be running based on the RUN
ENABLE status.
DAY.NIGHT
This is 1 of 5 mandatory FLN points required for
compatibility with Siemens control systems. It has no
functionality in the bypass application.
BYP RUN DLY
This allows FLN to delay running of the system after a run
command has been issued.
BYPASS MODE
This point indicates the Hand/Off/Auto status of the bypass.
0=OFF; 1=HAND; 2=AUTO.
ACH550 E-Clipse Bypass User's Manual
Description
Drive
Parameter
5002
0102
0101
0105
0106
0108
0111
0112
0113
1614