2-240
HP
3
5
7.5
10
15
20
25
30
40
50
60
75
100
1. "xxR" represents VCR, VDR, BCR and BDR.
2. UL Type/NEMA 3R enclosed units are provided with Bussman Type JJS or equivalent fuses. Fuse
ratings shown relate to latest production. Where installed product includes fuses of a lower rating,
either rating may be used.
380...480 volt fuses
HP
1/1.5
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
125
150
200
Technical data
208... 240 Volt
1
Identification
ACH550-xxR-012A-2
ACH550-xxR-017A-2
ACH550-xxR-024A-2
ACH550-xxR-031A-2
ACH550-xxR-046A-2
ACH550-xxR-059A-2
ACH550-xxR-075A-2
ACH550-xxR-088A-2
ACH550-xxR-114A-2
ACH550-xxR-143A-2
ACH550-xxR-178A-2
ACH550-xxR-221A-2
ACH550-xxR-248A-2
380... 480 Volt
1
Identification
ACH550-xxR-03A3-4
ACH550-xxR-04A1-4
ACH550-xxR-06A9-4
ACH550-xxR-08A8-4
ACH550-xxR-012A-4
ACH550-xxR-015A-4
ACH550-xxR-023A-4
ACH550-xxR-031A-4
ACH550-xxR-038A-4
ACH550-xxR-045A-4
ACH550-xxR-059A-4
ACH550-xxR-072A-4
ACH550-xxR-078A-4
ACH550-xxR-097A-4
ACH550-xxR-125A-4
ACH550-xxR-157A-4
ACH550-xxR-180A-4
ACH550-xxR-246A-4
ACH550 E-Clipse Bypass User's Manual
Drive Input Fuse Ratings
Frame
Amps
Size
(600V)
R1
15
R1
30
R2
30
R2
60
R3
100
R3
100
R4
100
R4
200
R4
200
R6
200
R6
315
R6
315
R6
315
Drive Input Fuse Ratings
Frame
Amps
Size
(600V)
R1
15
R1
15
R1
15
R1
15
R1
15
R2
30
R2
30
R3
60
R3
60
R3
60
R4
100
R4
100
R4
100
R4
200
R5
200
R6
200
R6
315
R6
315
Bussmann
Type
KTK-R-15
KTK-R-30
KTK-R-30
JJS-60
JJS-100
JJS-100
JJS-100
2
170M1370
or
170M2617
2
170M1372
or
170M2619
Bussmann
Type
KTK-R-15
KTK-R-15
KTK-R-15
KTK-R-15
KTK-R-15
KTK-R-30
KTK-R-30
JJS-60
JJS-60
JJS-60
JJS-100
JJS-100
JJS-100
2
170M1370
or
170M2617
2
170M1372
or
170M2619