ABB ACH550-UH User Manual page 459

Ach550 series, hvac drives (1...550 hp), e-clipse bypass drives (1...400 hp), packaged drives with disconnect (1...550 hp)
Hide thumbs Also See for ACH550-UH:
Table of Contents

Advertisement

ACH550 E-Clipse Bypass User's Manual
Number
AI14
AI15
AI16
AI17
AI18
AI19
AI20
AI21
AI22
AI23
AI24
AI25
1.
RATED SPEED
and is a percent of maximum speed (parameter 2002) in speed mode.
N2 binary input objects – drive
The following table lists the N2 Binary Input objects defined for the ACH550 drive.
Number
BI1
BI2
BI3
BI4
BI5
BI6
BI7
BI8
BI9
BI10
BI11
BI12
BI13
BI14
BI15
BI16
BI17
BI18
BI19
Object
PRC PID DEVIATION
EXT PID FEEDBACK
EXT PID DEVIATION
LAST FAULT
PREV FAULT
OLDEST FAULT
AI 1 ACTUAL
AI 2 ACTUAL
AO 1 ACTUAL
AO 2 ACTUAL
MOTOR TEMP
REVOLUTION CNT
is a percent of maximum frequency (parameter 2008) if the drive is in scalar mode,
Object
STOP/RUN
FORWARD/REVERSE
FAULT STATUS
RELAY 1 STATUS
RELAY 2 STATUS
RELAY 3 STATUS
RELAY 4 STATUS
RELAY 5 STATUS
RELAY 6 STATUS
INPUT 1 STATUS
INPUT 2 STATUS
INPUT 3 STATUS
INPUT 4 STATUS
INPUT 5 STATUS
INPUT 6 STATUS
EXTERNAL 2 SELECT
HAND/AUTO
ALARM
MAINTENANCE REQ
N2 Analog Inputs:
Drive
Scale
Parameter
Factor
0132
10
0131
10
0133
10
0401
1
0402
1
0403
1
0120
10
0121
10
0124
10
0125
10
0145
1
0142
1
N2 Binary Inputs:
Drive Parameter
Status Word
0 = Stop, 1 = Drive Running
Status Word
0 = Forward, 1 = Reverse
Status Word
0 = OK, 1 = Drive Fault
0122 (bit mask 04)
0 = Off, 1 = On
0122 (bit mask 02)
0 = Off, 1 = On
0122 (bit mask 01)
0 = Off, 1 = On
0123 (bit mask 04)
0 = Off, 1 = On
0123 (bit mask 02)
0 = Off, 1 = On
0123 (bit mask 01)
0 = Off, 1 = On
0118 (bit mask 04)
0 = Off, 1 = On
0118 (bit mask 02)
0 = Off, 1 = On
0118 (bit mask 01)
0 = Off, 1 = On
0119 (bit mask 04)
0 = Off, 1 = On
0119 (bit mask 02)
0 = Off, 1 = On
0119 (bit mask 01)
0 = Off, 1 = On
Status Word
0 = EXT1 = EXT2
Status Word
0 = AUTO, 1 = HAND
Status Word
0 = OK, 1 = ALARM
Status Word
0 = OK, 1 = MAINT REQ
2-113
Units
Range
%
0...100
%
0...100
%
0...100
fault code
fault code
fault code
%
0...100
%
0...100
mA
0...20
mA
0...20
°
C
0...200
MREV
0...32767
Range