ABB ACH550-UH User Manual page 419

Ach550 series, hvac drives (1...550 hp), e-clipse bypass drives (1...400 hp), packaged drives with disconnect (1...550 hp)
Hide thumbs Also See for ACH550-UH:
Table of Contents

Advertisement

ACH550 E-Clipse Bypass User's Manual
Group 17: Override 2
Code
Name
1701
OVERRIDE 2
1702
RUN EN OVR
1703
ST EN1 OVR
1704
ST EN2 OVR
1706
ST EN4 OVR
1707
FAULTS OVR
1708
OVRD2 MODE
Note: For wiring requirements and additional configuration detail refer to
Programming Advanced Override (Override 2)
Group 30: Fault Function
Code
Name
3001
UL ACTION
3002
UL TIME
3003
UL TRIP %
Group 17: Override 2
Resolution
Range
1
0 = NOT SEL
1 = DI5
2 = COMM
1
0 = ACKNOWLEDGE
1 = DISREGARD
1
0 = ACKNOWLEDGE
1 = DISREGARD
1
0 = ACKNOWLEDGE
1 = DISREGARD
1
0 = ACKNOWLEDGE
1 = DISREGARD
1
0 = ACKNOWLEDGE
1 = DISREGARD
1
1 = BYPASS
2 = VFD
3 = VFD/BYPASS
4 = STOP
Group 30: Fault Function
Resolution
Range
1
0 = NOT SEL
1 = FAULT
2 = WARNING
1 sec
10 - 400 sec
1%
0 - 100%
Default
Description
NOT SEL
Selects source for override 2
(0)
command.
DISREGA
Acknowledge or disregard run
RD
enable during override 2.
(1)
DISREGA
Acknowledge or disregard start
RD
enable 1 during override 2.
(1)
DISREGA
Acknowledge or disregard start
RD
enable 2 during override 2.
(1)
DISREGA
Acknowledge or disregard start
RD
enable 4 during override 2.
(1)
DISREGA
Acknowledge or disregard
RD
overrideable bypass faults during
(1)
override 2.
All faults can be overrode except:
3009, 3021, 3022, 3023, 3024,
3027, 3034, 3101, 3202, 3203,
3204, 3205, 3206
BYPASS
1 = Use bypass contactor only
2 = Use drive only
(1)
3 = Use drive, switch to bypass
on drive fault
4 = Both contactors open
on page 2-40.
Default
Description
NOT SEL
Selects action to be taken if
( 0)
underload occurs.
20 sec
Time below underload level
before fault is declared.
20%
Sets power level at which
underload is declared.
2-73
Parameters